DSpace
 

Researchspace >
General science, engineering & technology >
General science, engineering & technology >
General science, engineering & technology >

Please use this identifier to cite or link to this item: http://hdl.handle.net/10204/1625

Title: Type I fitting of copper tubes from a water distribution system
Authors: Fernandes, PJL
Keywords: Corrosions
Pitting corrosions
Issue Date: Mar-1998
Publisher: Peramon-Elsevier Science Ltd
Citation: Fernandes, PJL. 1998. Type I fitting of copper tubes from a water distribution system. Engineering failure analysis, vol 5 (1), pp 35-40
Abstract: This article discusses the outcome of an investigation of the failure of copper tubes from cold water distribution system carrying potable water in a shopping centre. Samples of copper tubes from a cold water distribution system which had failed due to pitting whilst in service were subjected to a detailed failure investigation. Analysis of the tubes showed that failure was a result of Type I pitting attack. While the exact cause of pitting was unknown, it was hypothesized that it could have been due to changes in the water quality and/or content. The tubes were found to be made from phosphorus de-oxidized copper and no anomalies were evident in either the chemical composition or the microstructure which could have caused the pitting observed. It was recommended that the tubes be replaced and that due attention be given to ensure that the new tubes are free of internal carbonaceous deposits or other foreign matter.
URI: http://hdl.handle.net/10204/1625
http://hdl.handle.net/10204/1625
ISSN: 1350-6307
Appears in Collections:Pollution and waste
Mining and geoscience
General science, engineering & technology

Files in This Item:

File Description SizeFormat
fernandez_1998.pdf411.29 kBAdobe PDFView/Open
View Statistics

Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.

 

Valid XHTML 1.0! DSpace Software Copyright © 2002-2010  Duraspace - Feedback